SCOPE OF APPLICATION

DZ30SLE is a very narrow A-type residual current circuit breaker. The width of the conventional 2P residual current circuit breaker is 81MM wide. Our product is only 18MM wide, which reduces the volume by 4 times and greatly increases the space utilization. This product is suitable for circuits with a working frequency of 50/60Hz, a rated working voltage of 230V or 110V, and a rated current of 10A-32A, in line with the international standard IEC61009-1.
AC type leakage circuit breaker: used for leakage protection of AC electricity; Type A leakage circuit breaker: It includes the protection function of AC type AC leakage current, and also has the protection function of pulsating DC leakage current; Remarks: Pulsating DC is some equipment that converts AC to DC, such as mobile phone chargers, electric vehicle chargers, switching power supplies, etc.

CONNECTION

Rated current In(A) Minimum Adapter Copper Wire
6 1 MM2/17AWG
10 1.5 MM2/16AWG
16 1.5 MM2/16AWG
25 2.5 MM2/13AWG
32 4 MM2/11AWG

MAIN TECHNICAL PARAMETERS

Rated Current 6A,10A,16A,25A,32A
Poles 1P+N
Rated Voltage Ue AC230V or AC400V
Insulation Voltage Ui 500V
Rated Impulse Withstand Voltage(1.2/50) Uimp 2kV
Rated Breaking Capacity 4500A
Rated residual operating current L△n(mA): 15mA, 30mA, 100mA, 300mA
Rated frequency 50/60Hz
Leakage tripping Electronic Type
Dielectric Test Voltage At And Ind . Freq . For 1min 1kA
Protection Class IP20
Current Tripping Curve C-Curve (5-10ln)
Electrical Life 4000
Mechanical Life 20000
Installation 35MM DIN Rail Mount or M3 Screw Side Mount
Reference Temperature For Setting Of Thermal Element 30°C
Ambient Temperature -5°C~+40°C
Terminal Connection Type Phillips Screws
Adapter Cable 1-10mm2 7AWG
Tightening Torque 2.0N.M
Standards IEC61009-1

TEMPERATURE COMPENSATION

When the ambient temperature is not a benchmark of 30 degrees , the reference correction factor is as folows .

Ambient Temperature -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃
Current Correction Coefficient 1.25 1.2 1.15 1.10 1.05 1.00 0.95 0.90 0.85